Description
| Product Name | GW100UV Ultraviolet Flame Detector | GW100IR2N Dual-Band Infrared Flame Detector | |
|
Product Images |
![]() |
![]() |
|
| Performance characteristics | Wide field of vision, long distance | Wide field of vision, short distance | |
| Application areas | Industrial workshop | Machines, equipment, small spaces | |
| Detection angle | ≥120° | ≥100° | |
| Fire source situation | Detection distance (unit: meters) | Detection distance (unit: meters) | |
| gasoline |
0.1 square meter fireproof disc (0.3 meters x 0.3 meters) |
40 | 40 |
| n-Heptane | 50 | 45 | |
| diesel fuel | 40 | 40 | |
| kerosene | 40 | 40 | |
| Aviation kerosene | 40 | 40 | |
| Alcohol | 40 | 35 | |
| Isopropanol | 40 | 35 | |
| methanol | 35 | 30 | |
| polypropylene | 25 | 20 | |
| Paper | 30 | 30 | |
| methane | 0.5 meters (height) x 0.2 meters (width) gas flame | 25 | 35 |
| Liquefied petroleum gas propane | 25 | / | |
| hydrogen | 25 | / | |
| ammonia | 20 | / | |
| silane | 0.3-meter flame | 15 | / |
| Aluminum and magnesium metals | 15 | / | |
| size of fire plate | Response time | ||
| 0.3m x 0.3m gasoline fire | ≤20 seconds (high-speed version ≤ 1 second) | ||
| 0.7m x 0.7m gasoline fire | <10 seconds | ||
| hydrogen flame or metal flame | / | ||
| Output mode | 2 relay outputs | ||
| Operating voltage | DC 24±6V | ||
| Work environment | -10℃~55℃ (standard type) or -40℃~70℃ (enhanced type) 0~95%RH (non-condensing) | ||
| Explosion-proof certification | Exd II CT6 Gb | ||
| Protective entrance | IP66/IP67 | ||
| Electrical interface | 1 x NPT 1/2 | ||
| Housing materials | Cast aluminum | Cast aluminum | |
| aspect | 72 mm x 72 mm x 96 mm | 60mm x 60mm x 68mm | |
| weight | 0.5 kg | 0.4 kg | |
| Certification | CCC、SIL2、SIL3 | CCC | |